10/21/2009 6:36 PM | |
Joined: 1/18/2007 Last visit: 8/20/2015 Posts: 16 Rating: (3) | Hi, Just wondering if anyone has tried connecting Siemens S7-1200 to Wonderware InTouch SCADA. We desperately need to do this but looks like it may not be possible. Any ideas? Martin |
This contribution was helpful to1 thankful Users |
- Scada Software Intouch Wonderware
- Wonderware Intouch Scada software, free download For Windows 10
- Wonderware Intouch Scada Software Full Download
- Scada Software Wonderware
10/22/2009 12:53 PM | |
Joined: 5/28/2008 Last visit: 1/31/2019 Posts: 1341 Rating: (133) | Hi, sorry, don't know this system. But if Wonderware works with S7300/400, I think it can work with 1200 also. Try the same driver as for 300/400. regards |
This contribution was helpful toRadiohead airbag how am i driving raritan. 1 thankful Users |
10/22/2009 1:07 PM | |
Joined: 1/18/2007 Last visit: 8/20/2015 Posts: 16 Rating: (3) | Thanks Robster, I actually cracked it out this morning. You are correct. I used the same DASSIDirect driver for the S7-300 and set the Remote Rack and Slot to 0 and a default connection resourse of 3. Works very well. Regards Martin. |
This contribution was helpful to3 thankful Users |
Downloading Wonderware InTouch Thank you for using our software library. The legal way for you to obtain the software is to contact the developer for purchasing information. Wonderware InTouch - InTouch software provides graphic visualization which takes your operations management, control and optimization to a whole new level. Such as Wonderware HMI Reports, Gadget Wizards for Wonderware or Wonderware SIDirect DAServer, which might be similar to Wonderware InTouch. Intouch scada software, free download. InTouch Machine Edition is a natural extension of the current Wonderware HMI portfolio and the perfect complement for customers who already own Wonderware System Platform or Wonderware Historian. It provides embedded devices, local PC-based HMIs, SCADA systems with unique functionality for connecting automation systems end-to-end.
11/19/2009 4:37 PM | |
Joined: 11/19/2009 Last visit: 12/7/2018 Posts: 6 Rating: (0) | Hi there, I have the same requirement; Need to communicate with 4 S7-1200's connected via Profinet. I am waiting for Wonderware to confirm if their S7SIMATIC DA Server & CP5613 card will work. Is this something you looked into? Presumably your S7-1200 is fitted with a CSM1277 module? Richard |
11/19/2009 5:24 PM | |
Joined: 1/18/2007 Last visit: 8/20/2015 Posts: 16 Rating: (3) | Hi RichG, Dont bother waiting to here back from Wonderware. They will probably give the official line that it is not supported but it does work. The Wonderware DASSIDirect I/O driver works very well with the S7-1200. Just treat it asyou would aS7-300 with a rack and slot of 0. Use all the same adress item names as you would with a 300. Yes we included a CSM-1277. All working well now. Best of luck. Regards Martin. |
11/19/2009 5:36 PM | |
Joined: 1/18/2007 Download michael brecker licks pdf. Last visit: 8/20/2015 Posts: 16 Rating: (3) | Also, I dont think you need a dedicated CP. I/O driver with standard ethernet port on the SCADA PC will work fine. |
11/20/2009 10:30 AM | |
Joined: 11/19/2009 Last visit: 12/7/2018 Posts: 6 Rating: (0) | Hi Farlo, many thanks for that Richard |
3/18/2010 4:37 PM | |
Joined: 9/23/2005 Last visit: 8/28/2019 Posts: 3739 Rating: (1013) | Hi, The FAQ “How can you establish a connection between a S7-1200 PLC and SIMATIC NET OPC?” http://support.automation.siemens.com/BR/view/en/39960679(Intranet) shows how to communicate with SIMATIC NET OPC. The FAQ Flexible Decoding and Processing of Data Matrix Codes with S7-1200http://support.automation.siemens.com/BR/view/en/40603943 shows how PC Access could also be used. Despite of not 100% homologate, they work with some restrictions. The tip is to program a S7-300/400 connection and gives rack=0 and slot=1. |
Denilson Pegaia Siemens Industry Sector Technical Support | |
This contribution was helpful to2 thankful Users |
3/19/2010 10:33 AM | |
Snow leopard vmdk and darwin_snow isohunt. Joined: 11/19/2009 Last visit: 12/7/2018 Posts: 6 Rating: | Yes, as discussed further down in this thread the Archestra DASSIDirect DAServer works fine with the S7-1200. I have a Intouch 9.5 application chatting away happily to three S7-1200's as I type. Richard |
5/1/2014 11:29 AM | |
Joined: 4/30/2014 Last visit: 1/3/2015 Posts: 12 Rating: (0) | hi Farlo! can you give me ebook to config it! I'm really have problemwith connect S7-1200 in TIA PORTAL to intouchwonderware |
Posted by2 years ago
Archived
Does anyone use it?
Scada Software Intouch Wonderware
We are currently running one plant with Ignition and while Ignition is rather capable, we are finding some short comings and having some headaches. We are considering a switch to Wonderware for the next plant and I'm curious what the community has to say about their software.
Wonderware Intouch Scada software, free download For Windows 10
I've met with one of their team and overall they look pretty solid. Their reporting looks much nicer than Ignition's and a few of their other features/functions look promising. Just trying to get a gauge.
Wonderware Intouch Scada Software Full Download
Thanks.
![Wonderware Wonderware](/uploads/1/2/6/1/126194833/215908663.jpg)
Scada Software Wonderware
33 comments